Skip to main content
foodservicenerd
Opening & operating

Type 1 vs Type 2 Hood: Which Does Your Kitchen Need?

Reviewed against primary sources — the International Mechanical Code (IMC §507) and NFPA 96, manufacturer-listed hood data, and your local mechanical code. This is educational information, not professional engineering, legal, or code advice; verify with a licensed mechanical engineer or contractor and your local authority having jurisdiction (AHJ).
Type I vs Type II kitchen hoods: grease and smoke vs heat and moisture, duct and fire-suppression rules under IMC 507 and NFPA 96, and when ventless works.
Educational, not legal advice. Codes vary by jurisdiction — always confirm with your local health department and building authority (AHJ).
FoodServiceNerd EditorialResearched from the FDA Food Code, manufacturer specs & industry sourcesUpdated Aug 2026
Sources & standards

The technical guidance on this page reflects these published codes and standards, which your local authority (AHJ) adopts, amends, and enforces. It is educational, not engineering or legal advice — confirm the current requirements for your jurisdiction.

A Type I hood handles grease and smoke from fryers, ranges, griddles, and charbroilers; it needs grease filters, grease-rated ductwork, and a fire-suppression system. A Type II hood handles only heat, steam, and moisture from dishwashers, steamers, and some ovens, with no grease duct or suppression required.

The core difference

Under the International Mechanical Code (IMC) Section 507, commercial kitchen hoods are classified by what the appliance beneath them produces. A Type I hood is required where cooking equipment produces grease or smoke. A Type II hood is used over equipment that produces heat, steam, or moisture (or products of combustion) but no grease or smoke.

That single distinction — grease versus no grease — drives everything else: filters, duct construction, fire suppression, cleaning schedules, and cost. Getting the classification wrong is not just an inspection failure; a heat-only Type II hood installed over a fryer would have no grease filters and no fire-suppression system over a serious fire hazard.

Type I hoods: grease and smoke

Type I hoods go over grease- and smoke-producing appliances: deep fryers, open-flame ranges, griddles, charbroilers, woks, rotisseries, tilt skillets, and most non-microwave ovens used for high-volume cooking. Because they capture airborne grease, Type I systems are built for containment and cleaning.

Required features of a Type I system include:

  • Listed grease filters or baffles that separate grease from the airstream and drain it to a cup.
  • Grease-rated ductwork — continuously welded, liquid-tight, and pitched — built and cleaned to NFPA 96.
  • An automatic fire-suppression system (typically UL 300 wet chemical) covering the appliances, hood plenum, and duct.
  • Make-up air to replace the large volume of air the hood exhausts.

Type I hoods also carry the heaviest maintenance obligations, including scheduled exhaust-system cleaning under NFPA 96 based on how much grease the kitchen produces.

Type II hoods: heat, steam, and moisture

Type II hoods are for appliances that give off heat and moisture but not grease: commercial dishwashers, booster heaters, steam tables, steamers, pasta cookers, and ovens or kettles that produce steam or products of combustion without grease-laden vapor. There are two common subtypes in practice — condensate (dishwasher) hoods for steam, and heat/fume hoods for combustion products.

Because there is no grease to capture, Type II hoods are much simpler: they generally do not require grease filters, grease-rated welded duct, or a fire-suppression system. The IMC still requires the interior to have smooth, cleanable, water-tight joints and seams, and some heat-and-moisture loads can be handled by the building's HVAC design instead of a dedicated hood where the code allows. This is why Type II systems cost meaningfully less to install and maintain than Type I.

Ductwork and fire suppression for Type I

The reason Type I hoods are expensive is what happens above them. Grease duct under NFPA 96 must be liquid-tight and continuously welded, sloped to drain, provided with access panels for cleaning, and kept clear of combustible materials or protected by rated enclosure/wrap. The exhaust fan, duct, and hood plenum must all be cleanable and inspected on a schedule tied to grease volume.

Fire suppression is equally strict. A Type I hood typically carries a pre-engineered wet-chemical system listed to UL 300, with nozzles aimed at each appliance and at the plenum and duct, fusible-link heat detection, a manual pull station, and automatic shutoff of gas and electric power to the appliances when it discharges. These systems require semiannual inspection under NFPA 96 / NFPA 17A. None of this applies to a Type II hood — which is exactly why the classification matters so much.

When ventless (recirculating) is allowed

Some electric appliances can be used without a ducted hood if they use a factory-built recirculating system listed and labeled to UL 710B. These "ventless" units pull cooking effluent through built-in grease filtration and often catalytic and HEPA/charcoal stages, then return cleaned air to the room instead of ducting it outside. When listed to UL 710B and installed per the IMC, such systems are permitted without a separate NFPA 96 hood-and-duct system.

Important limits apply: recirculating systems are for electric appliances only, because their filters do not remove the products of combustion from gas equipment. Local authorities do not always accept ventless cooking, listings restrict which appliances and menu items are covered, and the units still demand diligent filter maintenance. Always confirm acceptance with your local code official before relying on a ventless solution.

Quick reference: Type I vs Type II

FactorType IType II
ProducesGrease and smokeHeat, steam, moisture (no grease)
Typical appliancesFryers, ranges, griddles, charbroilers, woksDishwashers, steamers, booster heaters, some ovens
Grease filters/bafflesRequiredNot required
DuctworkWelded, liquid-tight, NFPA 96 grease ductSimple, no grease-duct rules
Fire suppressionRequired (UL 300 wet chemical)Not required
Governing codeIMC 507, NFPA 96, NFPA 17AIMC 507.3
Relative costHighLow

When in doubt, classify by grease: if the appliance can throw grease into the airstream, plan for a Type I system.

Sources

Frequently asked

What is the difference between a Type 1 and Type 2 hood?
A Type I hood is required over grease- and smoke-producing appliances (fryers, ranges, griddles, charbroilers) and needs grease filters, welded grease duct, and fire suppression. A Type II hood handles only heat, steam, and moisture (dishwashers, steamers) and needs none of those grease systems.
Does a dishwasher need a Type 1 or Type 2 hood?
A commercial dishwasher produces heat and steam but no grease, so it uses a Type II (condensate) hood, not a Type I. Type II hoods do not require grease filters, welded grease ductwork, or a fire-suppression system, which makes them much cheaper to install and maintain.
Does a Type 2 hood need fire suppression?
No. Because a Type II hood is used over heat-, steam-, and moisture-producing equipment that does not create grease or smoke, IMC 507 does not require grease filters, grease-rated duct, or an automatic fire-suppression system. Fire suppression is a Type I requirement under NFPA 96.
When can I cook without an exhaust hood?
You can skip a ducted hood only when using a factory-built recirculating (ventless) system listed and labeled to UL 710B, installed per the IMC. These work for electric appliances only, are subject to local acceptance and listing limits, and are not permitted for gas equipment. Confirm with your local code official first.
Which codes govern commercial kitchen hoods?
The International Mechanical Code (IMC) Section 507 classifies hoods and sets ventilation rules; NFPA 96 governs grease exhaust duct construction, cleaning, and fire protection; NFPA 17A and UL 300 cover wet-chemical suppression; and UL 710B covers recirculating ventless systems. Local amendments can be stricter.

Related guides