Grease Trap Cleaning: The 25% Rule and Schedule

Reviewed against primary sources — the Uniform/International Plumbing Code, the FDA Food Code, and manufacturer specifications. This is educational information, not professional engineering, legal, or code advice; verify with a licensed professional and your local authority having jurisdiction (AHJ).
Learn the 25% rule for grease traps, how often to pump one out, who does the work, and what records your local sewer authority expects you to keep.
Educational, not legal advice. Codes vary by jurisdiction — always confirm with your local health department and building authority (AHJ).
FoodServiceNerd EditorialResearched from the FDA Food Code, manufacturer specs & industry sourcesUpdated Aug 2026
Sources & standards

The technical guidance on this page reflects these published codes and standards, which your local authority (AHJ) adopts, amends, and enforces. It is educational, not engineering or legal advice — confirm the current requirements for your jurisdiction.

Have a grease trap pumped before the combined grease and solids reach 25% of its liquid depth (the 25% rule). Many jurisdictions require gravity interceptors pumped at least quarterly and small hydromechanical traps monthly, but your local sewer authority sets the binding schedule.

Why FOG control matters

Fats, oils, and grease, collectively called FOG, pour down the drain as warm liquid and then cool and congeal inside pipes and sewers. Over time they build up, restrict flow, and cause sanitary sewer overflows. A grease trap or grease interceptor is a plumbing device that slows wastewater long enough for grease to float to the top and solids to settle to the bottom, so only relatively clean water continues to the sewer.

That is why nearly every municipality with a sewer system runs a FOG control program and requires food service establishments to install, maintain, and document a grease interceptor. The EPA regulates these discharges under the Clean Water Act, but the specific rules, sizing, and pump-out frequency are set locally by your sewer authority or authority having jurisdiction (AHJ).

Traps come in two broad types. Small hydromechanical grease interceptors (HGIs), often installed indoors under or near a sink, are compact and fill quickly. Larger gravity grease interceptors (GGIs), typically buried outside, hold far more volume and are pumped less often. Both work on the same principle of separation, and both are governed by the same maintenance standard covered next.

The 25% rule explained

The core maintenance standard across the industry is the 25% rule, sometimes called the one-quarter rule. It states that when the combined thickness of the floating grease layer and the settled solids reaches 25% of the trap's total liquid depth, the device must be pumped out and cleaned.

The logic is capacity. A grease interceptor is only designed to retain grease up to a point; once accumulation passes roughly a quarter of the working volume, the trap can no longer separate incoming wastewater effectively and grease begins to carry over into the sewer line. The 25% threshold builds in a conservative safety margin and appears in industry standards and municipal codes nationwide. It is measured with a dip stick or sludge-judge probe lowered into the trap, not guessed at from the top, since the settled solids layer at the bottom is invisible from above.

How often to pump out

The 25% rule sets the trigger; your fixture type, size, and menu determine how fast you hit it. A high-volume fryer-heavy kitchen with a small under-sink trap can reach 25% in a week, while a large exterior interceptor may take months. Local codes translate this into a maximum interval regardless of fill:

Interceptor typeTypical minimum pump-out
Small hydromechanical (indoor) trapOften every 30 days
Large gravity interceptor (exterior)Often every 90 days
Any device at the 25% levelImmediately, whichever comes first

Treat these as common examples, not universal law: your permit or ordinance states the binding frequency for your address. When in doubt, pump on the more frequent schedule and adjust based on how full the trap actually is at each service.

Who does the work and what to keep

Grease trap pumping is done by a licensed liquid-waste or grease hauler. They fully pump the device, scrape the walls and baffles, inspect for damage, and haul the waste to an approved disposal or rendering facility. A proper cleaning removes the entire contents, not just the floating grease, so solids do not accumulate at the bottom over time.

  • Full pump-out, not skimming. Skimming only the top layer leaves solids behind and shortens the effective life of the trap.
  • Keep the manifests. Retain the hauler's service records and waste manifests; most FOG programs require you to produce them on demand and keep them for a set number of years.
  • Do not use enzymes or additives as a substitute. Products that claim to dissolve grease often just push it downstream, where it re-congeals in the sewer, and many jurisdictions prohibit them.

Know your local authority

Because grease requirements are AHJ-driven, the single most useful step is to contact your municipal sewer authority, wastewater utility, or building department and ask for the local FOG ordinance. It will tell you the required interceptor size, the mandated pump-out frequency, the recordkeeping period, and the penalties for a blocked or overflowing trap, which can be substantial.

Build the schedule into your kitchen's routine the way you would any other preventive maintenance, alongside hood cleaning and equipment service. A well-maintained grease trap protects your plumbing, keeps you compliant, and avoids the far larger cost of a backup during service. For the broader kitchen build, see our guides on flooring and equipment selection.

Sources

Frequently asked

What is the 25% rule for grease traps?
The 25% rule says a grease trap must be pumped out and cleaned once the combined floating grease and settled solids reach 25% of the trap's total liquid depth. Past that point the device can no longer separate grease effectively and it starts carrying over into the sewer. It is measured with a probe, not estimated.
How often should a restaurant pump its grease trap?
It depends on size, menu, and local code. Many jurisdictions require small indoor hydromechanical traps pumped roughly monthly and large exterior gravity interceptors at least quarterly, or sooner if the trap hits the 25% level. Your local sewer authority or permit sets the binding frequency, so confirm the requirement for your address.
Who cleans a commercial grease trap?
A licensed liquid-waste or grease hauler. They fully pump the device, scrape the baffles and walls, inspect it, and haul the waste to an approved disposal or rendering facility. They also provide a service manifest, which most FOG control programs require you to keep on file for inspection.
Do grease trap enzymes or additives work?
They are not a substitute for pumping. Enzyme and bacteria additives generally emulsify grease so it flows past the trap, where it re-congeals downstream in the sewer and can cause blockages. Many municipal FOG ordinances specifically prohibit additives used to avoid required pump-outs. Mechanical cleaning is the compliant method.
What records do I need to keep for grease trap cleaning?
Keep every hauler service record and waste manifest showing the date, volume removed, and disposal site. FOG programs typically require you to retain these for a set number of years and produce them during inspection. Consistent records also prove your pump-out schedule is adequate if a dispute or fine arises.